NC-01 is a device that enables the communication between isolated APN network and other network using RS485 or RS422 standard.

NC-01 connects with an APN network using GSM 2G technology and GSM operator’s infrastructure. Access to the APN network is acquired via a VPN tunnel.

How it works: NC-01 connection

NC-01 can work in three modes:

  1. Transparent mode – all bytes are sent between networks without making any changes in them.
  2. MODBUS protocol mode – this mode enables sending data using MODBUS TCP or MODBUS RTU over TCP protocol to a RS485/RS422 network that uses MODBUS RTU protocol.
  3. Marked frame mode – data string begins with one or two characters that identify the beginning of a frame and it ends with one or two characters identifying the end of a frame.

NC-01 provides solutions when there is a need of connecting local devices with centralized SCADA systems or other devices and networks.

Application

  • water supply networks
  • sewage treatment plants
  • gas supply networks
  • energy networks
  • heating networks
  • telemetric systems

Advantages:

  • low implementation and maintenance costs
  • small dimensions
  • simple configuration
  • easy mounting
Parameter nameValue
Dimensions36x90x70 mm
MountingDIN35 rail
Power supply voltage12-24V DC
Power supplymax 0.5 A (24V)
Serial interfaceRS485/RS422 max. 115 kbps
GSM ranges850/900/1800/1900 MHz
Type and speed of GSM transmissionGPRS – 85.6 kbps
GSM card typeNano SIM